top of page
05cb58d1ccy.png

Fire Rated Glass

Specifications

  • Fire resistance (EN 1363-1) : Up to E 240

  • Reaction to fire (EN 13501-1) : A1

  • Testing Standard : Tested in accordance with BS EN 1634-1: 2000, UL 9, UL10B, UL10C, NFPA 252, NFPA 257 UL/NFPA, up to 180 minutes, BS EN up to 240 minutes

  • Maximum Glass Size : Variable, subject to glass make-up, framing material or glazed element type.

  • Thickness tolerance : ±0.2 mm

  • Length tolerance : ±2 mm

  • Hazardous material contained : None

  • Nominal thickness : 5 mm

  • Glass size per thickness : ≤ 1150 mm x 2000 mm

  • Fire protection : both sides

  • Weight : 13 kg/m2

  • Sound reduction Rw (EN 140-3) : 32 dB*

  • Light transmission (EN 410) : 89%

  • Light reflection rL (exterior/interior) : 8%/8%

  • U value, W/m2K (EN 673): 5,8

  • g value : 0,86

  • Energy transmission tE : 84%

  • Energy reflection rE (exterior/interior): 8%/8%